Products
Interface Converters

RS-485/422/232 Multimode

RS-232 to RS-485/422

RS-485/422 to RS-485/422

Accessories

120V at 3W Wall-Plug

220V at 3W Wall-Plug

90 to 264V at 3W Wall-Plug

DIN Rail Adapter

Gender Changer

Cable

 Printer Friendly Version

RS-485/422 Repeater/Converter
        

Isolated Not Isolated
    
Item No. Price

IC100-RXX

$108.00


Isolation

RS-485/422 Termination Plug

Quantity:

All Prices are in US Dollars.
    

Parallel Entry

 

    
This RS-485/422 to RS-485/422 converter automatically controls RS-485 transmitter-enable independent of baud rate, without software or jumpers. It automatically controls the direction of serial data eliminating the need for software flow control, uses a patented technique to  automatically adapt to any baud rate up to 115,200 baud and is independent of communications protocol. It has a max range of 4000 feet and operating temperature of -25°C to 80°C.  Choose isolated or not isolated, and parallel or vertical entry for the RS-485/422 termination plug. It has a stainless steel enclosure and operates from a 9-24 Vac - Vdc wall plug adapter.

    
Features
  • Omni-Isolation™ Optical and transformer isolation technology provide up to 2000 volts of signal and ground isolation between the computer and equipment. Eliminates ground loops that destroy computer ports and reduce serial communications reliability.

  • ADFCADFC (Automatic Data Flow Control), uses a technique protected by U.S. patent no. 5,729,547 that automatically senses and controls the direction of RS-485 data eliminating the need for software control.

  • 3-in-1 Signal Conversion Converts RS-232 to RS-485, RS-232 to RS-422 or RS-485 to RS-422. Automatically senses RS-422 four-wire operation.

  • Status LEDs Status LEDs are provided on both sides of the isolation for the Power, Transmit and Receive signals. These are handy for verifying operation and troubleshooting network problems.

  • Transient Voltage Protection All signal and power lines are protected against transient voltages.

  • Switch Selectable Termination and Bias Resistors Network termination and bias can easily be configured with DIP switches available from the outside the converter case. The switches are clearly identified on the label for easy setup.

  • DTE-DCE Selection A switch easily makes the ESI either a DTE or a DCE device so the unit will communicate with a DCE or DTE device, or operate with a “straight-through” or “null modem” cable.

  • Echo With the echo feature enabled, data is echoed back to the equipment side port. This may desirable or required with some protocols. The default is no echo.

  • Baud Rate Independent No switches or jumpers to set. Automatically adapts to all standard and non-standard baud rates up to 115,200 baud.

  • Versatile Power Supply The unit can be powered by a wide range of AC or DC voltages. Wall-plug adapters are available from duTec or others. A pluggable screw terminal is also provided for use with other power supplies. 7 to 24 volts AC or 9 to 36 volts DC @ 120mA max.

  • Pluggable Terminal Blocks Industrial rated pluggable terminal blocks for ease of installation or removal. Accepts up to 16 AWG wire.

  • DIN Rail Mounting DIN Rail mounting accessories available for easy wiring. 

    
Specifications

    

Isolation

Omni-isolationTM provides 4-way isolation using optical and transformer technology. Equipment-to-Line, Equipment-to-Power, Line-to-Power, Equipment-to-Chassis, Line-to-Chassis, Power-to-Chassis. 
Hi-Pot: 2000 VRMS for 1 minute, 5500 VDC for 1 second Leakage Current: Less than 50uA @ 2000 VAC / 60 Hz; 5500 VDC

Baud Rates

0 to 115.2K bps

Range

4000 feet (1220 meters) @ 38.4K bps with 24 AWG twisted pair

Weight

12.8 oz. (363 grams)

Power

9 to 24 volts AC or DC @ 170mA (max)

Enclosure

18 gage Stainless Steel

Dimensions

Height: 4.60 inches (117mm)
Depth: 4.16 inches (106mm)
Width: 1.00 inch ( 25mm)

RS-485/422

Supports RS-422, 4 or 2 wire and RS-485, Auto Detect Input Resistance: 12K to 15K ohms (1 unit load) Drive: Up to 32 unit loads (1 unit load = 12K ohms) Connector: Pluggable Terminal Blocks (#16 to #24 AWG) Biasing Resistors: Selectable 100K or 1.2K ohms Terminating Resistors: Selectable NONE, AC or DC

RS-485 Enable

Automatic. Patented ADFC™ technology automatically controls data direction flow.

Operating Temperature

-20°C to +80°C

Storage Temperature

-45°C to +100°C

Humidity

5% to 95% RH

Compliance

Pending (CE, FCC Class A, CUL, UL Safety Class II)

Accessories

DIN Rail Mounting Kit: Part No DA-01 
AC Power Adapter: North American: 120 VAC Input 
AC Power Adapter: European: Universal Input: 90-264 VAC Input

Surge Protection

600 Watt Transient Voltage Suppression on RS-485/422 inputs and outputs, RS-232 inputs and outputs and Power input.

Indicators

Equipment Side: Power, RxD, TxD LEDs 
Line Side: Power, RxD, TxD LEDs

        
Applications

    

RS-232/422/485 Isolators / Converters / Repeaters

Line Extender

Troubleshooting Tool

Y Networks

Short Haul Modems

      
Dimensions

    
Click to Enlarge Image
  
© 2004 ESI